Watts Tekmar Mixing Control 360

Mixing Control 360

The Mixing Control 360 is purpose-built to manage a mixing valve utilizing Outdoor Temperature Reset functionality. Its applications range from in-floor radiant heating to commercial baseboard systems, offering comprehensive Boiler Return Protection with full reset capability. This control ensures the regulation of a single heating water temperature through Mixing Outdoor Reset. It governs the mixing process by adjusting a floating action type mixing valve actuator (compatible with 3 or 4-way valves) and provides oversight of the mix system pump.

Key Features:

  • Outdoor temperature reset functionality optimizes heating performance in response to outdoor conditions
  • Optional indoor temperature feedback enhances control precision (requires indoor sensor)
  • Warm weather shutdown feature prevents unnecessary heating during warmer periods
  • Automatic boiler differential ensures efficient boiler operation
  • Floating action mixing control mechanism maintains temperature regulation
  • Powered mixing system pump output streamlines system management
  • Quick setup facilitates easy installation and programming
  • User comfort adjustment enables fine-tuning of building space temperatures
  • Advanced settings allow customization to meet specific building requirements
  • Test sequence functionality ensures proper component operation
  • Setback input promotes energy savings by adjusting heating levels
  • CSA C US certified, meeting applicable UL standards for safety and reliability.

Specifications

Agency Approvals CSA C US, meets class B: ICES & FCC Part 15
Ambient Conditions Indoor use only, 32 to 104 degrees F (0 to 40 degrees C), RH less than or equal to 90 percent Non-condensing
Control Type Microprocessor control, this is not a safety (limit) control
Demand 20 to 260 V (ac) 2 VA
Dimensions 6 5/8 IN H x 7 9/16 IN W x 2 13/16 IN D (170 x 193 x 72 MM)
Enclosure Material Blue PVC plastic
Enclosure NEMA Rating NEMA 1
Floating Output 24 V (ac) 0.34 A 8 VA
Hydronic – HVAC Control Type Mixing Control
Power Supply 120 V (ac) plus / minus 10 percent, 50/60 Hz, 1300 VA
Relay 240 V (ac) 10 A 1/3 hp
Sensor NTC thermistor, 10 k ohms at 77 degrees F (25 degrees C plus / minus 0.2 degrees C) Beta=3892